Aali Services
Engineering Insights

Chiller / Facility Performance

6 Warning Signs Your Chiller Is Losing Performance

Chiller performance can deteriorate gradually while the system continues providing cooling. Learn six warning signs facility and maintenance teams should monitor.

ChillerAug 27, 202615 min read
Industrial chiller equipment illustrating six warning signs of declining chiller performance
Illustrative engineering image highlighting common chiller performance warning signs.

A chiller does not need to stop working completely before it develops a performance problem.

In many facilities, deterioration happens gradually. The chiller continues providing cooling, but it begins operating differently: chilled-water temperature becomes harder to maintain, electrical consumption rises, heat-transfer performance changes, or the equipment starts and stops more frequently.

These changes do not automatically mean the chiller has a major fault. What matters is whether operating conditions are changing from the system's established baseline under comparable conditions.

For facility managers and maintenance teams, recognizing these trends early creates an opportunity to investigate the cause before declining performance becomes a larger reliability or operating-cost problem.

Here are six warning signs worth monitoring.

1. The Chiller Is Struggling to Maintain Chilled-Water Supply Temperature

One visible indication of changing chiller performance is difficulty maintaining the required chilled-water supply temperature. If it now struggles to achieve the same condition under broadly comparable operating circumstances, the change deserves investigation.

ASHRAE's chiller fault-detection guidance includes chilled-water supply temperature being too high among conditions evaluated when assessing chiller-plant operation.

Possible areas to investigate include:

  • Chilled-water flow
  • Evaporator heat transfer
  • Refrigerant-side conditions
  • Compressor operation
  • Sensors and controls
  • Setpoints
  • Actual cooling load
  • System sequencing

What has changed compared with normal operation?

2. Electrical Consumption Is Rising for Similar Cooling Demand

A chiller can continue delivering cooling while requiring more electrical energy. Compare performance under similar conditions rather than comparing monthly electricity totals alone.

Useful questions include whether electrical demand is increasing at comparable chiller load, whether operating hours are increasing, whether condenser-water conditions changed, and whether heat-transfer conditions deteriorated.

ASHRAE's guidance for liquid-chilling systems emphasizes monitoring operating conditions and keeping daily operating logs.

What to Monitor

  • Chiller electrical demand
  • Cooling load
  • Operating hours
  • Chilled-water supply and return temperatures
  • Condenser-water temperatures
  • Water flow
  • Relevant refrigerant pressures and temperatures
  • Ambient or process conditions where applicable

Monitor

Chiller electrical demandCooling loadOperating hoursChilled-water temperaturesCondenser-water temperaturesWater flow

3. Condenser Approach Temperature Is Increasing

Condenser approach gives maintenance teams information about how effectively heat is transferred through the condenser. ASHRAE's chiller fault-detection guidance identifies high condenser approach as a condition that can warrant investigation.

An increasing condenser approach can potentially be associated with condenser-tube fouling, scale, water-flow problems, water-treatment conditions, refrigerant-side issues, non-condensable gases or sensor problems.

ASHRAE's condenser guidance explains that increased condenser fouling increases resistance to heat transfer.

4. Evaporator Approach Temperature Is Increasing

Evaporator approach can provide useful information about heat transfer on the cooling side of the chiller. Possible areas for investigation include evaporator surfaces, chilled-water flow, refrigerant conditions, sensor accuracy, water-side conditions and actual chiller load.

Observation A

Evaporator approach is higher than expected today.

Observation B

Evaporator approach has gradually increased over several months while load and chilled-water conditions remained broadly comparable.

The second observation is more diagnostically useful.

5. The Chiller Is Starting and Stopping More Frequently

ASHRAE's chiller-plant fault-detection guidance includes too many chiller starts and changes in operating state among conditions that can be monitored.

Possible areas to investigate include low or unstable cooling load, chiller sizing, plant sequencing, control settings, multiple-chiller staging, chilled-water flow, system volume and setpoint interactions.

6. Condenser Fouling, Scale or Water-Quality Problems Are Increasing

For water-cooled chillers, condenser-water condition is closely connected to heat-transfer performance. The loop may face scaling, corrosion, suspended solids, fouling or microbiological activity.

ASHRAE recommends proper water treatment and regular tube cleaning for liquid chillers. The U.S. Department of Energy's cooling-water guidance explains that fouling and scaling can form insulating material on heat-exchanger surfaces.

Warning Signs Worth Investigating

  • Increasing condenser approach
  • Visible scale or deposits
  • Frequent condenser cleaning requirements
  • Deteriorating water-quality results
  • Sediment accumulation
  • Biological fouling
  • Increasing condensing pressure or temperature
  • Changes in cooling-tower performance

Don't Judge Chiller Performance From One Reading

Modern chiller systems contain many interacting variables. A single measurement can be misleading without operating context. ASHRAE recommends maintaining operating logs to show trends and provide advance notice of deteriorating conditions.

Establish what normal looks like. Then investigate meaningful deviations from that baseline.

What Should Your Maintenance Team Trend?

ParameterWhat It Helps You Understand
Chilled-water supply temperatureWhether required cooling conditions are being maintained
Chilled-water return temperatureCooling-load and system behavior
Chilled-water flowWater-side and heat-transfer conditions
Condenser-water entering/leaving temperaturesHeat-rejection conditions
Condenser approachCondenser heat-transfer performance
Evaporator approachEvaporator heat-transfer performance
Chiller electrical demandEnergy input
Chiller loadContext for comparing energy and performance
Starts and operating hoursCycling and equipment utilization
Water chemistryScale, fouling and corrosion risk
Alarm historyRecurring operating abnormalities

Chiller Performance Is a Plant Issue, Not Just a Compressor Issue

Plant System View

Chiller
Chilled-Water System
Condenser-Water System
Cooling Tower
Water Treatment
Controls and Sequencing
Building or Process Load

Chiller

The compressor, evaporator, condenser, refrigerant circuit and controls determine much of the equipment's core operation.

Chilled-Water System

Water flow, pumps, differential pressure, bypass arrangements and control valves influence how cooling is distributed.

Condenser-Water System

For water-cooled systems, condenser-water flow and temperature directly influence heat rejection.

Cooling Tower

Tower condition, airflow, fan control and outdoor wet-bulb conditions influence the temperature of water returning to the condenser.

Water Treatment

Scaling, corrosion, suspended solids and biological growth can affect heat-transfer surfaces and system reliability. DOE identifies corrosion, scaling, fouling and microbiological activity as important treatment concerns.

Controls and Sequencing

Setpoints, staging logic, sensors and plant sequencing determine when equipment starts, stops and changes operating state.

Building or Process Load

Ultimately, the plant responds to the cooling demand placed upon it.

When Should You Consider a Chiller Performance Assessment?

A closer assessment may be worthwhile when chilled-water temperature is difficult to maintain, electrical consumption is rising, condenser or evaporator approach has changed, starts have increased, scale is suspected, water-quality problems recur, cooling capacity deteriorates or alarm frequency increases.

Not Sure How Your Chiller Is Actually Performing?

Aali Services provides chiller inspection, preventive maintenance and performance-assessment support for industrial and commercial facilities in Saudi Arabia. Our engineering team can review chilled-water performance, condenser and evaporator conditions, heat transfer, water conditions, operation, controls and preventive maintenance requirements.

Technical References

  1. 01ASHRAE - Guideline 36 Addendum: Chiller Plant Fault Detection
  2. 02ASHRAE Handbook - Liquid-Chilling Systems
  3. 03ASHRAE Handbook - Condensers
  4. 04U.S. Department of Energy - Cooling Tower Side Stream Filtration
chiller performancechiller maintenanceindustrial chillerpreventive maintenanceHVAC maintenancewater treatment
Share LinkedIn

Concerned About Your Boiler or Chiller Performance?

Aali Services can assess equipment condition and help identify practical performance improvements.